Herunterladen Diese Seite drucken

Siemens SIPART PS2 EE d Serie Montage-Und Installationsanleitung Seite 34

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

6
Pneumatic Connection
(see Figure 13, page 60 -- in Appendix)
Warning
!
For safety reasons, after assembly, the pneumatic supply may only be connected if the positioner is
switched to the operating level "P manual mode" in the presence of an incoming electrical signal (for
the status at delivery, see leaflet "Operation – a concise overview").
.
Note
Ensure that the air quality is suitable! Grease-free industrial air, particulates < 30 mm, pressure dew
point 20 K below lowest ambient temperature.
Connect gauge for inlet air pressure and positioning pressure if necessary.
D
Connection
D
Order no.
6DR4005-1E
6DR4005-2E
6DR4105-1E
6DR4105-2E
6DR4005-1EN
6DR4005-2EN
6DR4105-1EN
6DR4105-2EN
PZ
Inlet 1.4 to 7 bar
Y1
Positioning pressure 1 for single-action and double-action actuators
Y2
Positioning pressure 2 for double-action actuators
E
Exhaust output (remove splash protection if necessary)
Safety setting on failure of electric supply:
D
Single--action:
Double--action:
Connect positioning pressure Y1 and Y2 (only with double-action actuators) according to desired safety
D
setting.
Connect inlet air to PZ.
D
7
Commissioning (see Leaflet "Operation – a concise overview")
Because of the numerous possible applications, the positioner must be individually adapted to the actuator
after assembly (initialized). This initialization is largely automatic. The positioner calculates the direction of
action, the travel and the angle or rotation and the travel times of the actuator, one after the other.
Before initialization, you only have to set a few parameters for the positioner. The remaining parameters are
set with default values that you do not normally have to alter. If you observe the following points, you will not
have any problems during commissioning.
Tip: You can return to the previous parameter by pressing the
38
via female thread
1
G
/
DIN 45141
4
1
/
-14 NPT
2
in acc. with ANSI / ASME B1.20.1 – 1983
Y1
Y1
Y2
Vented
Max. positioning pressure (inlet air pressure)
Vented
and
keys simultaneously.
C79000-M7474-C157-01

Werbung