Herunterladen Diese Seite drucken

Siemens SIPART PS2 EE d Serie Montage-Und Installationsanleitung Seite 28

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

3.2
Extension Kit "Linear actuator" 6DR4004-8V and 6DR4004-8L
The following are included in the delivery of the extension set "Linear actuator IEC 534 (3 mm to 35 mm)"
(see Figure 1, page 33 for item nos.):
Item No.
Qty.
Designation
1
1
NAMUR mounting bracket IEC
534
2
1
Pick-up bracket
3
2
Clamping assembly
4
1
Driver pin
5
1
Roll
6
1
NAMUR lever
7
2
U-bolt
8
4
Hexagonal head screw
9
2
Hexagonal head screw
10
6
Lock washer
11
6
Flat washer
12
2
Flat washer
13
1
Spring
14
1
Spring washer
15
1
Lock washer
16
3
Lock washer
17
3
Socket cap screw
18
1
Hexagonal nut
19
1
Square nut
21
4
Hexagonal nut
22
1
Guide washer
3.2.1
Assembly sequence
(see Figure 1, page 33)
1.
Mount clamping assembly (3) with socket cap screws (17) and lock washers (16) on the actuator spindle.
2.
Insert the pick-up bracket (2) into the recesses of the clamping assembly. Set the required length and
screw only so tight that the pick-up bracket can still be shifted.
3.
The center of the pin (4) is set to the value of the stroke range specified on the actuator or set to the
next large scale value. The same value can be set later for 3.YWAY during start-up, to display the travel
in mm after initialization.
4.
Push the lever onto the positioner shaft as far as possible, and secure with the socket cap screw (17).
5.
Fit the mounting bracket (1) with two hexagonal head screws (9), lock washer (10) and flat washer (11)
on the rear of the positioner.
6.
Selection of the row of holes depends on the width of the actuator yoke. The roll (5) should engage in the
pick--up bracket (2) as close to the spindle as possible, but must not touch the clamping assembly.
7.
Hold the positioner with the mounting bracket on the actuator such that the roll (5) is guided within the
pick-up bracket (2).
8.
Tighten the pick-up bracket.
9.
Position the mounting parts according to the type of actuator.
-- Actuator with ledge: hexagonal head screw (8), flat washer (11) and lock washer (10).
-- Actuator with plane surface: four hexagonal head screws (8) with flat washer (11) and lock washer (10).
-- Actuator with columns: two U-bolts (7), four hexagonal nuts (21) with flat washer (11) and lock
washer (10).
10. Secure positioner onto the yoke using the previously positioned mounting parts.
.
Note
Adjust the height of the positioner such that the horizontal lever position is reached as close as pos-
sible to the center of the stroke. The lever scale of the actuator can be used for orientation. Ensure
that the horizontal lever position is always passed through within the stroke range.
32
Remarks
Standardized connection for mounting console with ledge, column,
or plane surface
Guides the roll with driver pin and rotates the lever arm
Mounting of pick-up bracket on actuator spindle
Assembly with roll (5) on lever (6)
Assembly with driver pin (4) on lever (6)
For stroke range 3 mm to 35 mm
For stroke ranges > 35 mm to 130 mm (special delivery), lever
6DR4004-8L is also required
Only for actuators with columns
M8 x 20 DIN 933-A2
M8 x 16 DIN 933-A2
A8 -- DIN 127-A2
B 8.4 -- DIN 125-A2
B 6.4 -- DIN 125-A2
VD-115E 0.70 x 11.3 x 32.7 x 3.5
A6 -- DIN 137A-A2
3.2 -- DIN 6799-A2
A6 -- DIN 127-A2
M6 x 25 DIN 7984-A2
M6 -- DIN 934-A4
M6 -- DIN 557-A4
M8 -- DIN 934-A4
6.2 x 9.9 x 15 x 3.5
C79000-M7474-C157-01

Werbung

loading