3.3
Extension Kit "Rotary actuator" 6DR4004- - 8D
The following are included in the delivery of the extension kit "Rotary actuator" (see Figure 2, page 35 for item
nos.):
Item No.
Qty.
Designation
2
1
Coupling wheel
3
1
Driver
4
1
Multiple scale
4.1
8
Scale
4.2
1
Pointer
14
4
Hexagonal head screw
15
4
Lock washer
16
1
Fillister head screw
17
1
Flat washer
18
1
Set screw
19
1
Hex wrench
3.3.1
Assembly sequence
(see Figure 2, page 35)
1.
Place VDI/VDE 3845 mount ((9), actuator specific, supplied by the actuator manufacturer) onto rear of
positioner and secure using hexagonal head screws (14) and lock washers (15).
2.
Adhere pointer (4.2) onto mounting console in the middle of the centering hole.
3.
Push coupling wheel (2) onto positioner shaft as far as possible, pull back by about 1 mm, and tighten
set screw (18) with the angular screw driver supplied.
4.
Place the driver (3) onto the end of the actuator shaft and secure with the fillister head screw (16) and
flat washer (17).
5.
Carefully place positioner with the mounting console onto the actuator so that the pin of the coupling
wheel engages in the driver.
6.
Align the positioner/mounting console assembly in the center of the actuator and screw tight.
(Screws not included in the delivery; they are part of the actuator mounting console.)
7.
Following start-up as described in Chapter 7: drive actuator to end position and adhere scale (4.1)
onto the coupling wheel (2) according to the direction of rotation or the turning range. The scale is pre-
pasted!
4
Option modules
(see Figure 3, page 55 or Figure 4, page 56 -- in Appendix)
1.
Loosen the safety catch for end cover (12) and unscrew the end cover (11).
2.
Loosen screws (13.1), remove the base plate (13), if necessary rotate the actuator so that the clutch can
be easily separated.
3.
Loosen module fixing screws (1.1) and remove module cover (1).
4.
HART module (only for devices without PROFIBUS PA): Place the HART module (2) onto the plug
connector; first remove the plug-in jumper from the top connector.
5.
J
module: Insert the J
y
cable (6).
6.
Alarm module: Insert the alarm module (4) into the upper container slot; and connect using the supplied
ribbon cable (5).
7.
Mount the module cover (1) and the base plate (13).
8.
Screw on the end cover (11) and lock with the safety catch.
.
Note
Take care during assembly that all O-rings on the inside of the pneumatic connections are correctly
positioned.
34
Remarks
Mounting on position feedback shaft of SIPART PS2
Mounting on end of actuator shaft
Indication of actuator position, comprising 4.1 and 4.2
Different divisions
Reference point for marker (adhesive label)
DIN 933 -- M6 x 12
S6
DIN 84 -- M6 x 12
DIN 125 -- 6,4
Premounted with coupling wheel
For item 18
module (3) into the lower container slot, and connect using the supplied ribbon
y
C79000-M7474-C157-01