7.1.1
Initialization of linear actuators
If you can move the actuator correctly, leave it in a central position, and start automatic initialization:
1.
Press the mode key
Display:
2.
Switch to the second parameter by pressing the mode key
Display:
.
Note
This value must match the setting of the transmission ratio selector (7, Leaflet "Operation -- a
concise overview") (33° or 90°)
3.
Switch to the following display with the mode key
You only have to set this parameter if you want to have the calculated total stroke displayed in mm at the
end of the initialization phase. To do this, select the same value in the display as the value to which you
set the driver pin on the scale of the lever.
4.
Switch to the following display with the mode key
5.
Start initialization by pressing the
During the initialization process "RUN1" to "RUN5" appears one after the other in the lower display.
.
Note
The initialization process can take up to 15 min. depending on the actuator.
Initialization is complete when the following display appears:
After you have pressed the mode key
To exit Configuration mode, press the mode key
is displayed. After you have released the mode key, the unit is in manual mode. Pressing the mode key
briefly, you set the positioner back to the automatic mode.
If you want to set further parameters, refer to the leaflet "Operation -- a concise overview" (see page 47
following) or the Manual.
You can start reinitialization from manual or automatic mode at any time.
40
for more than 5 s. This takes you into Configuration mode.
key for more than 5 s:
briefly, the following display appears:
briefly.
or
:
:
for more than 5 s. After about 5 s, the software version
C79000-M7474-C157-01