INSTRUCTIONS AND WARNING FOR ADJUSTMENTS
WARNING: Before making any type
of adjustment, activate all the safety de-
vices provided and decide whether staff at
work and those in the vicinity should be in-
formed. In particular, turn off the gas and wa-
ter supply taps, cut off the electricity supply
using the master switch and prevent access
to all devices which might cause unexpected
health and safety hazards if turned on.
Carry out this operation as described on both
the gas solenoid valves.
Natural
Turn off the gas supply tap..
1)
Open the hatch (A).
2)
Unscrew the cap (D).
3)
Fully screw the adjusting screw (E).After ma-
4)
king the setting, seal the screw with paint.
Restore the initial conditions after comple-
5)
ting the operation.
Liquid gas
Turn off the gas supply tap.
1)
Open the hatch (A).
2)
Undo the screw (B) of the pressure connec-
3)
tion.
Connect the pressure gauge (C) to the pres-
4)
sure test point.
Unscrew the cap (D).
5)
Turn the gas supply tap back on.
6)
14
ADJUSTMENTS
ADJUSTING GAS VALVE (0*1FR1G - 1*1FR2G)
NOTE: This adjustment is only re-
quired if the type of gas to be connected is
diff erent from that used for testing after the
conversion procedure has been carried out
(see page 13).
WARNING: Adjustments must be car-
ried out by authorised, qualifi ed staff , in ac-
cordance with the relevant legal require-
ments.
A
C
B
Light the burner and turn the screw (E) until
7)
the pressure gauge shows the pressure re-
commended in the table of injectors at the
back of the manual.
Check the stability of the fl ame.
8)
After making the setting, seal the screw with
paint.
Turn off the burner, disconnect the pressure
9)
gauge and restore the initial conditions after
completing the operation.
ADJUSTMENTS
D E
3269850_inst_GB_rev.3