Balluff BTL7-A/C/E/G5 M J-DEXC-TA12 Serie Betriebsanleitung Seite 64

Magnetostriktives positionsmesssystem
Vorschau ausblenden Andere Handbücher für BTL7-A/C/E/G5 M J-DEXC-TA12 Serie:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
BTL7-A/C/E/G5_ _-M_ _ _ _-J-DEXC-TA12
Magnetostrictive Linear Position Sensor – Rod Style
13
Type code
Interface:
A = Analog interface, voltage output 0...10 V
G = Analog interface, voltage output –10...+10 V
C = Analog interface, current output 0...20 mA
E = Analog interface, current output 4...20 mA
Supply voltage:
5 = 10...30 V DC
Output gradient:
00 = Rising (e.g. C_00 = 0...20 mA); only with BTL7-C/E
10 = Rising + falling (e.g. A_10 = 10...0 V and 0...10 V); only with BTL7-A/G
70 = Falling (e.g. C_70 = 20...0 mA); only with BTL7-C/E
Nominal length (4-digit):
M0500 = Metric specification in mm, nominal length 500 mm (M0025...M7620)
Rod version, fastening:
J = 6 screws (hole circle 76.2 mm)
Plug:
C = Float plug
Electrical connection:
TA12
= Terminal with 1/2"-14 NPT (conduit entry)
Order example for special version (optional, no influence on Ex characteristics):
BTL7-A510-M0500-J-DEXC-SA_ _ _-TA12
30
english
Type of protection "db" and "t"
BTL7 - A 5 10 - M0500 - J - DEXC - TA12
Flameproof enclosure