Herunterladen Diese Seite drucken

Balluff BTL7-A/C/E/G5 M J-DEXC-TA12 Serie Betriebsanleitung Seite 59

Magnetostriktives positionsmesssystem
Vorschau ausblenden Andere Handbücher für BTL7-A/C/E/G5 M J-DEXC-TA12 Serie:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
BTL7-A/C/E/G5_ _-M_ _ _ _-J-DEXC-TA12
Magnetostrictive Linear Position Sensor – Rod Style
10
Resetting all values (reset)
NOTICE
Interference in function
Resetting the values while the system is running may
result in malfunctions.
► Stop the system before performing the reset.
The reset function can be used to restore all the settings to
the factory settings. For a reset the magnet may also be
located outside the measuring range.
1. Activate buttons
► Activate any button for at least 3 s.
► Release buttons.
► Simultaneously (within 1 s) activate
least 3 s.
⇒ Output indicates error value.
⇒ Buttons are activated.
If an error or an interruption occurs while
activating the buttons, allow a wait time of 12 s
before retrying.
2. Reset
► Activate
a
b
and
for at least 6 s.
⇒ Output indicates null value.
⇒ All values are reset.
► Release buttons.
⇒ Current position value is displayed.
⇒ Buttons are locked.
www.balluff.com
> 3 s
< 1 s
a
b
and
for at
> 3 s
> 6 s
Type of protection "db" and "t"
Flameproof enclosure
Displayed values (example)
At 0 to 10 V
a
b
a
b
10.50 V
a
b
At 4 to 20 mA
5.39 V
10.80 mA
5.39 V
10.80 mA
3.60 mA
0.00 V
4.00 mA
8.43 V
15.67 mA
english
25

Werbung

loading

Diese Anleitung auch für:

Btl7-a -m -j-dexc-ta12 serieBtl7-c -m -j-dexc-ta12 serieBtl7-e -m -j-dexc-ta12 serieBtl7-g5 -m -j-dexc-ta12 serieBtl7-a510- serieBtl7-g510- serie ... Alle anzeigen