7.1.3
Measured value scaling
Name
Measured value decimal point
'DIDP'
Measured value 0 % 'DILO'
Measured value 100 % 'DIHI'
Measured value offset 'OFFST'
"
Caution!
Measured value 0 % and 100 % may not be identical. However, the 0 % measured value can be
larger than the 100 % measured value (invert).
7.2
Display (DISPL)
7.2.1
Dimension
DIM É Options: NO, °C, K, °F, % or TEXT
One of the units permanently stored in the display can be selected - K, °C, °F, %. Alternatively, any
unit can be configured on the 14-segment display (TEXT).
The character set consists of the following characters:
Characters A-Z and a-z, digits 0-9 and special characters: blank, (, ), -, +, /, &, >, <, =, \
Description
Indicates the number of places after the decimal point for the numerical display of the
measuring range.
– Selection range 0 - 3 places after decimal point
– Default: 1 place after decimal point
If the number of spaces after the decimal point is increased, the value for all the
dependent operating parameters must be recalculated based on the formula new value
(PDnew - PDold)
= old value * 10
. If the value of one of the dependent operating
parameters is < -19999 or > 99999, the number of places after the decimal point
cannot be increased and error message E290 is shown on the display.
Indicates the display value for the 4 mA value.
– Value range -19999 to 99999
– Default: 0.0
Indicates the display value for the 20 mA value.
– Value range -19999 to 99999
– Default: 100.0
This is used to correct the display measured value. The offset is added to the measured
value.
– Value range -19999 to 99999
– Default: 0.0
Device configuration
53