Herunterladen Diese Seite drucken

Endress+Hauser RIA141 Bedienungsanleitung Seite 52

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Device configuration
52
• Device parameter data storage
• Measuring point documentation
Further in-depth information on operation via ReadWin
documentation on the software. The latest version of ReadWin
charge from the Internet at the following address:
www.endress.com/ReadWin
7
Device configuration
Description of operating functions
The following table shows the menus available for the field indicator. These are explained in detail
in the sections specified.
Section
Section 7.1
Section 7.2
Section 7.3
Section 7.4
Section 7.5
7.1
Data processing (INPUT)
7.1.1
Input range
INPUT É CURVE É Options: Linear (LINAR) or square root (SQRT).
The input range is a 4 - 20 mA signal.
Select the type of input signal here (linear or quadratic).
7.1.2
Damping
INPUT É DAMP É Options: 0 - 99 (0 = no damping)
• Measured value damping can be set between 0 and 99 s.
• Only whole numbers can be entered.
• The factory setting is 0 (no damping).
®
2000 can be found in the online
Function
Data processing
Display
Limit values
Other settings
Service level
®
2000 can be downloaded free of
As shown on the display
INPUT
DISPL
LIMIT
PARAM
SERV

Werbung

loading