Radiator heating
system
H-
H+
Pump
Yonos PICO.../1-6 m
Underfloor heating
H-
H+
Pump
Yonos PICO.../1-6 m
36
7.2
Setting the control mode and the delivery head
The size of the displayed house symbols and data for
setting the delivery head are provided as a guide only.
A more detailed calculation for the setting is recom-
mended. The values of the delivery head are displayed in
increments of 0.1 m with the setting.
Variable differential pressure (Δp-v):
• Select the setting range of the application.
• Set setpoint H of the delivery head (variable differen-
tial pressure).
The LED display shows the setpoint H of the delivery
head in m.
Number of radiators
I
12
Constant differential pressure (Δp-c):
• Select the setting range of the application.
• Set setpoint H of the delivery head (constant differ-
ential pressure).
The LED display shows the setpoint H of the delivery
head in m.
Number of square metres of heated space in m²
I
80
II
15
II
150
III
20
III
220