High-pressure section

The leak test of the high-pressure section can be performed by the
user�
4.4

Low-pressure section

WARNING
Risk of fire or explosion hazard
If the leak test is not performed properly on the low-pressure
section, leaks may remain undiscovered�
Only have the gas system checked by an expert�
For experts only
Test conditions:
Maximum test pressure 150 mbar
The high-pressure hose and gas cylinder must be connected�
Switch off all the gas appliances such as the heating, refrigerator
or gas hob in the recreational vehicle�
Open all quick-acting shut-off valves to the gas appliances and, if
necessary, the gas remote switch�
Disconnect the low-pressure section from the high-pressure
section� To do this, push in the triggering element for the crash
sensor until the yellow reset button jumps out�
Unscrew the screw cap of the test connection�
Connect the regulator test appliance with the test hose to the test
connection�
Check for leaks in accordance with the national regulations
(e�g� 607 in Germany)�
Unscrew the regulator test appliance from the test connection�
50020-00976 ∙ 00 ∙ 08/2022