Water treatment
If this is connected in the replenishment line, and the IWZ is also set to ON, the amount of residual
water that can still be treated with the water treatment module can be read off in litres in the
process menu. At 0 litres, the collective error message is triggered and an error message is issued.
Negative values mean that the permissible treatment quantity (capacity) in litres has been exceeded.
However, even when this collective error message has been triggered, replenishment still remains in
operation. The water treatment function must be activated by the operator.
Control type (replenishment operation)
The operator can operate the system by means of level control (externally controlled via an external
replenishment control system) or pressure control
(standard setting for normal gas-cushioned MAG).
Operating mode
The operator has the option of operating the system in automatic mode, fill mode or manually.
refer to section: Mode of operation of NFE + MVE1
Sensor
This is not relevant for MVE1 and does not need to be parameterised.
Motor protection
This is not relevant for MVE1 and does not need to be parameterised.
Collective error message
In the case of ON (ticked), the collective error message is triggered when the scheduled maintenance
date is reached. However, even when the date is exceeded the system remains in operation.