INSTALLATIoN

disposal

xxx Fault
Effect
205 Maximum
The high limit safety cut-
outdoor air
out may respond.
temperature
exceeded
Program-
Parameters cannot be
ming unit
adjusted.
does not
start.
Sensor resistance values
Note
When measuring with a multimeter, the resistance values
serve only to identify faulty or incorrect sensors. Measur-
ing with a multimeter is too imprecise to test for accuracy.
Supply air
Exhaust air
Temperature [°C]
-30
-20
-10
0
10
20
25
30
40
50
60
70
80
90
100
110
120
www.stiebel-eltron.com
Remedy
Isolate the appliance from the
power supply. Check the triac
for continuity. Check the sensor
cable.
2
I
C-connection faulty: Check cable
and plug-in connections. Replace
damaged cable.
Sensor type
PT 1000
PT 1000
PT 1000
Resistance [Ω]
882
922
961
1000
1039
1078
1097
1117
1155
1194
1232
1271
1309
1347
1385
1423
1461
LWZ 180 | LWZ 280 | LWZ 180 Enthalpie | LWZ 280 Enthalpie |
16. Disposal
Dismantling
WARNING Electrocution
Disconnect the appliance from the power supply.
The following tools are required for disassembly and material
separation prior to disposal:
- Personal protective equipment
- Set of screwdrivers
- Set of spanners
- Combi pliers
- Stanley knife
59