STIEBEL ELTRON LWZ 180 Bedienung Und Installation Seite 54

Zentrales lüftungsgerät mit wärmerückgewinnung
Vorschau ausblenden Andere Handbücher für LWZ 180:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

INSTALLATIoN
Settings
Heat recovery bypass
Window contact mode (depending on unit)

Setting whether the window contact is relevant for the bypass
mode.
Parameter
Effect
Without window
The supply air fan is stopped independently of the win-
contact
dow contact.
With window con-
The window contact is used to determine whether the
tact
appliance stops the supply air fan.

Temperature to enable heat recovery bypass
To enable checking of the other parameters for bypass mode, the
outdoor air temperature must be no less than the value set in
this parameter.
Temperature to block heat recovery bypass

If the outdoor air temperature falls below this blocking tempera-
ture, bypass mode is disabled.

Hysteresis for heat recovery bypass
To make cooling possible, the outdoor air temperature must be
cooler than the extract air temperature by the value set in this
parameter.

Temp. differential for heat recovery bypass
Use this parameter to define the temperature differential that must
be exceeded for bypass mode to be enabled. For bypass mode to
be enabled, the following condition must be met for 60 minutes:
If Operating mode heat recovery bypass: Outdoor air routing au-
tomatic
- Set room temperature + Temp. differential for heat recovery
bypass < Outdoor air temp.
If Operating mode heat recovery bypass: Extract air routing autom.
- Set room temperature + Temp. differential for heat recovery
bypass < Extract air temp.
Frost protection

Temperature for enabling frost protection
The unit only activates frost protection if the outdoor air temper-
ature drops to the value that can be set in this parameter.
Enable preheating

Parameter
Effect
Off
The internal preheater is completely deactivated.
On
The internal preheater is activated. To keep the heat ex-
changer free from ice, preheating ensures a minimum
supply air temperature with reference to the temperature,
which can be set in the "Frost protection temp." parameter.
While this parameter is being displayed or adjusted, the "frost
protection" symbol is shown on the display.
54
| LWZ 180 | LWZ 280 | LWZ 180 Enthalpie | LWZ 280 Enthalpie

Frost protection mode
Parameter
Effect
Outdoor air reg. At this setting, the appliance operates solely in frost protec-
tion mode. The preheating coil control only measures the
outside temperature.
Supply air reg.
At this setting, the appliance operates in comfort mode. In
addition to the outside temperature, the supply air tempera-
ture is also measured.
Passive house
The preheating coil is controlled to ensure that the supply
reg.
air temperature does not fall below the 16.5 °C specified in
the passive house criteria.
Condensate prevention
Enable condensate prevention

The Condensate prevention function is intended for units without
an enthalpy heat exchanger in areas with a subtropical climate.
If the unit is in ventilation mode, and this parameter has the value
"On", the unit checks the following conditions:
- Outdoor air temp. > Extract air temp.
- Extract air temp. + Offset condensate prevention < Outdoor
air dew point
If both conditions are met, the unit switches the fans off. After
a shutdown, the unit switches on the fans cyclically and checks
whether the conditions are still valid or whether ventilation mode
can be resumed.
Interval between measurements
Duration of measurement

Offset condensate prevention
This parameter changes the shutdown point for Condensate pre-
vention. This allows the fans to be switched off 2 K before the dew
point temperature is reached, for example.
Ventilation unit
Device type

This parameter is set at the factory. The parameter can only be set
after the controller assembly has been replaced.
min
60
min
5