oPErATIoN
Maintenance, cleaning and care
Note
At times where there is no time program defined, the
appliance runs in set fan stage 2.
Example
Time scale
Monday - Friday
06:00 - 22:00
22:00 - 06:00
Saturday , Sunday
07:00 - 23:00
23:00 - 07:00
x
x.1
day or group of days Fan stage
1 1/2/3/4/5
2 1/2/3/4/5
3 6/7
4 6/7
4.5.4 Code
„Cod
You can use this menu item to enable actual values and parame-
ters, which are reserved for qualified contractors.
Effect
A0 The only parameters displayed are those that have been released for the
appliance user and can therefore be accessed without a code.
A1 Parameters for qualified contractors
A2 Parameters for service department
A1 or A2 is shown on the display when you enter the correct
four-digit code.
If you switch to the actual values or parameters, you see the en-
abled parameters.
Note
After entering the code, switch to the menu by pressing
the "MENU" button. If you first switch to the standard
display by pressing the "HOME" button, the parameter
block is reactivated.
4.6

Switching off the appliance

The appliance has no ON/OFF switch. Disconnect the power supply
by pulling the power plug from its socket.
www.stiebel-eltron.com 
stage
2
1
2
1
x.2
x.3
x.4
start time stop time
1
22:00
00:00
1
00:00
06:00
1
23:00
00:00
1
00:00
07:00
LWZ 180    /   L WZ 280 / LWZ 180 Enthalpie / LWZ 280 Enthalpie  | 
5.

Maintenance, cleaning and care

Maintenance by the user is limited to filter inspection and replace-
ment required at certain intervals.
5.1

Replacement filters

Product 
Part 
description
name
number
FMS G4-10 180
234147
Coarse particle filter mat ISO Coarse > 60 % (G4)
FMK M5-2 180
234148
Fine filter
FMK F7-2 180
234208
Fine filter
5.2

Filter inspection and replacement

Material losses
!
Never operate the appliance without filters.
f Inspect the filters for the first time three months after com-
missioning the appliance.
When the total fan runtimes reach the "Filter change interval"
value, which can be set by the qualified contractor, the program-
ming unit displays the "Filter" symbol.
The qualified contractor can lengthen or shorten the interval for
inspecting filters depending on the level of contamination.
The "filter" symbol appears after a time set by the qualified con-
tractor.
If the "filter" symbol illuminates, check the filters. Change the
filters if the surface is covered completely in dirt or the filter is
discoloured throughout.
Change the filters at least every 12 months.
Filter inspection
f Pull the mains plug out of the socket.
3.
1 Extract air filter
2 Outdoor air filter
3 Knurled screw for securing the filter drawer
4 Fascia
5 Locking tabs
The fascia is fastened to the appliance with locking tabs.
f To disengage the locking tabs, press the grip areas on the
fascia sides.
ePM
≥ 50 % (M5)
10
ePM
≥ 50% (F7)
1
1
2
3
4
5
2.
1.
5
35