oPErATIoN
settings
At times where there is no time program defined, the appliance
runs in set fan stage 2.
4.5

Menu

display
description
P1 - Pxx Parameter
I1 - Ixx
Actual values
Pro
Programs
Cod
Entry of the code for unlocking protected parameters and actual
values
f To access the parameters, press the "MENU" button.
The "HOME" button takes you to the standard display. If you have
not changed any settings for a while, the appliance automatically
switches back to the standard display.
4.5.1 Parameter
description
options
P1 Set room temperature
P2 This parameter defines
the runtime for intensive
ventilation. After this time
has expired, the appliance
returns to the previously
applicable fan stage. If
the intensive ventilation
is switched on with an
external switch, this pa-
rameter defines how long
the intensive ventilation
continues to run after
opening the switch.
P3 Bypass mode
0  | 1  | 2 | 3
P4 Reset filter
1 | 0
P28 Enable fan
On  | OFF
P80 Day
P81 Time
P82 Level of lighting
P83 Mode of backlighting
Auto | On | OFF
P84 Illumination duration
P85 Lower standard display
OFF | Time  | Set
room temperature  |
Extract air temper-
ature  | Extract air
humidity
In order to set the parameter, you must first make it editable by
pressing the "OK" button. Then you can change the value with
the Touch-Wheel. If you do not press the "OK" button to make the
parameter editable, activating the Touch-Wheel causes the next
parameter to be displayed.
Press the "OK" button to save the set value for a parameter. If you
do not confirm the parameter change with the "OK" button, your
change will be lost.
„P1: Set room temperature
Use this parameter to set the outside temperature from which
the bypass damper ensures that outdoor air bypasses the heat
exchanger and flows directly into the building.
www.stiebel-eltron.com 
„P3: Bypass mode
0 The bypass is permanently disabled. Air flows through the heat exchanger.
1 The bypass is active. The air flow bypasses the heat exchanger.
2 The bypass operates with summer day detection. This option is set in the
3 The bypass operates subject to the extract air temperature.
P3 = 2 : Bypass with summer day detection
unit Min. Max. stand-
For the bypass to be activated, the following condition must apply
ard
for 60 minutes: Outdoor air temperature > Set room temperature
°C
5
28
20
+ P27
Min. 1
240
30
If all the following conditions are met, the appliance switches to
bypass mode.
- Outdoor air temperature < Extract air temperature - P26
- Extract air temperature > Set room temperature
If one of the following conditions is met, the appliance terminates
bypass mode.
- Outdoor air temperature < P25
- Outdoor air temperature > Extract air temperature - P26
2
- Extract air temperature < Set room temperature
On
P3 = 3 : Bypass subject to extract air temperature
1
7
00:00 23:59
For the bypass to be activated, the following condition must apply
2
10
10
for 60 minutes: Extract air temperature > Set room temperature
Auto
+ P27
s
10
500
60
This delayed enabling prevents cooling down in spring and au-
OFF
tumn.
If all the following conditions are met, the appliance switches to
bypass mode.
- Outdoor air temperature < Extract air temperature - P26
- Extract air temperature > Set room temperature
If one of the following conditions is met, the appliance terminates
bypass mode.
- Outdoor air temperature < P25
- Outdoor air temperature > Extract air temperature - P26
- Extract air temperature < Set room temperature
„P4: Reset filter
f Set this parameter to 1 after changing the filters. The appli-
LWZ 180    /   L WZ 280 / LWZ 180 Enthalpie / LWZ 280 Enthalpie  | 
Effect
delivered condition.
Note
The qualified contractor can set the parameters men-
tioned in the description of this parameter.
P24: Bypass enable temperature
P25: Bypass blocking temperature
P26: Bypass hysteresis
P27: Temperature differential for enabling the bypass
ance resets the filter runtime to 0. This parameter is auto-
matically reset to 0.
33