How to connect wiring to the terminal

■ For stranded wiring

(1) Cut the wire end with cutting pliers,
then strip the insulation to expose
the stranded wiring about 10 mm and
tightly twist the wire ends. (Fig. 4-5)
(2) Using a Phillips head screwdriver,
remove the terminal screw(s) on the
terminal plate.
(3) Using a ring connector fastener or
pliers, securely clamp each stripped
wire end with a ring pressure terminal.
(4) Place the ring pressure terminal,
and replace and tighten the removed
terminal screw using a screwdriver.
(Fig. 4-6)

■ Examples of shield wires

(1) Remove cable coat not to scratch braided shield. (Fig. 4-7)
(2) Unbraid the braided shield carefully and twist the
unbraided shield wires tightly together. Insulate the shield
wires by covering them with an insulation tube or wrapping
insulation tape around them. (Fig. 4-8)
(3) Remove coat of signal wire. (Fig. 4-9)
(4) Attach ring pressure terminals to the signal wires and the
shield wires insulated in Step (2). (Fig. 4-10)

■ Wiring sample

Functional ground screw
(Schedule Timer)
Protective ground screw
(External Solenoid Valve Kit for 3WAY)
Power
supply
cord
Stranded wire
Ring
pressure
terminal
Fig. 4-5
Use this screw when
connecting the
shield for the inter-
unit control wiring to
ground
Remote control wiring
Inter-unit control wiring
14
Special
Screw
washer
Ring pressure
terminal
Terminal plate
Wire
Wire
Fig. 4-6
Fig. 4-7
Insulation tape
Fig. 4-8
Insulation tape
Fig. 4-9
Fig. 4-10
Screw and
Special washer
Ring
pressure
terminal