How to connect wiring to the terminal

■ For stranded wiring

(1) Cut the wire end with cutting pliers,
then strip the insulation to expose
the stranded wiring about 10 mm and
tightly twist the wire ends. (Fig. 4-7)
(2) Using a Phillips head screwdriver,
remove the terminal screw(s) on the
terminal board.
(3) Using a ring connector fastener or
pliers, securely clamp each stripped
wire end with a ring pressure terminal.
(4) Place the ring pressure terminal,
and replace and tighten the removed
terminal screw using a screwdriver.
(Fig. 4-8)

■ Examples of shield wires

(1) Remove cable coat not to scratch braided shield. (Fig. 4-9)
(2) Unbraid the braided shield carefully and twist the
unbraided shield wires tightly together. Insulate the shield
wires by covering them with an insulation tube or wrapping
insulating tape around them. (Fig. 4-10)
(3) Remove coat of signal wire. (Fig. 4-11)
(4) Attach ring pressure terminals to the signal wires and the
shield wires insulated in Step (2). (Fig. 4-12)
■ Wiring sample
F1 type
Use this screw when connecting the shield
for the Inter-unit control wiring to ground.
Protective ground screw
Stranded wire
Special
washer
Ring
pressure
terminal
Wire
Fig. 4-7
Functional ground screw
Power Supply
14
Screw
Ring pressure
terminal
Terminal board
Wire
Fig. 4-8
Fig. 4-9
Insulating tape
Shield mesh
Fig. 4-10
Insulating tape
Shield mesh
Fig. 4-11
Fig. 4-12
Remote Control
Wiring
Inter-unit Control
Wiring
Screw and
Special washer
Ring
pressure
terminal