Adjustment - Pilz PSEN cs1.13p ATEX Bedienungsanleitung

Vorschau ausblenden Andere Handbücher für PSEN cs1.13p ATEX:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

PSEN cs1.13p ATEX
Procedure:
Fig.: Sensing faces on the sensor
1. Drill holes (for M5 screws) in the mounting surface to secure the actuator and sensor
(see
2. Use a screw to fix the sensor to the mounting surface.
Make sure that the sensor marking that is be used for operation can be operated using
the actuator from the right side.
3. Do not fully tighten the second screw on the safety switch.
4. Use a screw to fix the actuator to the mounting surface.
Make sure that the actuator with the printed side points towards the marking on the
sensor.
5. Do not fully tighten the second screw on the actuator.
6. Align the safety switch and tighten the screws.
7. Align the actuator and tighten the screws.

Adjustment

}
The stated operating distances (see
safety switch and actuator are installed facing each other in parallel. Operating dis-
tances may deviate if other arrangements are used.
}
Note the maximum permitted lateral and vertical offset (see Operating distances and
Lateral and vertical offset [
Operating Manual PSEN cs1.13p ATEX
21097-2EN-13
CAUTION!
Change of the release distance S
If you install the safety switch non-flush within electrically or magnetically
conductive material, the value for the assured release distance S
change.
Dimensions in mm [
with non-flush installation
ar
42]).
Technical details [
34]).
can also
ar
43]) only apply when the
40