4. Use a screw to fix the actuator to the mounting surface.
Make sure that the actuator with the printed side points towards the marking on the
sensor.
5. Do not fully tighten the second screw on the actuator.
6. Align the safety switch and tighten the screws.
7. Align the actuator and tighten the screws.

Adjustment

The stated operating distances (see
}
safety switch and actuator are installed facing each other in parallel. Operating dis-
tances may deviate if other arrangements are used.
Note the maximum permitted lateral and vertical offset (see Operating distances and
}
Lateral and vertical offset [

Operation

Status indicators:

"Power / Fault" LED illuminates green: The unit is ready for operation
}
"Safety Gate" LED lights up yellow: Actuator is within the response range
}
"Input" LED lights up yellow: There is a high signal at both inputs
}
Error display through periodic flashing:
"Input" LED lights up yellow: The signal switches from high to low at one input, while a
}
high signal remains on the other input (partial operation).
Remedy: Open both channels of the input circuit.
"Power/Fault" LED lights up red: Error message
}
Flashing codes for fault diagnostics are output to the "Safety Gate" or "Input" LED (see

Error display through flashing codes).

Remedy: Rectify fault and interrupt power supply.
Please note the different times for
The switch-on delay after UB is applied
}
The recovery time of the sensor and evaluation device.
}
Error display through flashing codes
The "Safety Gate" and "Input" LEDs send flash signals; an error code can be established
from the number and sequence. The "Power/Fault" LED illuminates red.
Operating Manual PSEN cs2.13p ATEX
21133-2EN-1
34]).
NOTICE
The safety function should be checked after initial commissioning and each
time the plant/machine is changed. The safety functions may only be
checked by qualified personnel.