Automatic Operation; Manual Operation - socomec ATyS p M Installationshandbuch Und Bedienungsanleitung

Automatische lastumschalter
Vorschau ausblenden Andere Handbücher für ATyS p M:
Inhaltsverzeichnis

Werbung

5
Programming
To access programming
Default code: 1000
1
2
1
2
1
2
1
2
1
2
TIMERS
1FT
Loss of source 1 Validation timer.
1RT
Source 1 return validation timer.
2FT
Loss of source 2 Validation timer.
2RT
Source 2 return validation timer.
2AT
Standby network stability validation before transfer.
2CT
Run on timer.
ODT
Dead band timer.
PARAMETERS
Neutral position on the switch
AUTO: neutral position is automaticaly detected when the
product is supplied the first time.
NEUTRAL
LEFT: neutral must be connected to the left that means
on the terminal 1 from each switch.
RIGHT: neutral must be connected to the right that means
on the terminal 7 from each switch.
Nominal voltage
NOM. VOLT.
Phase/phase or phase/neutral in 1BL and 41NBL
NOM. FREQ.
Nominal Frequency
Type of application
APP
M-G: network - Genset
M-M: network - network
Retransfer inhibit feature, press on Validation button
RETRANS
required to allow retransfer form Gen to Main
NETWORK
Network configuration*
(1) O to 3600 secs in M-M network
* The wiring must be adapted to the network configuration. Below, the main configuration types.
3 phase / 4 wire
3 phase / 3 wire
1
4NBL
3NBL
4BL
3BL
N
3
2
CORPORATE HQ CONTACT: SOCOMEC SAS, 1-4 RUE DE WESTHOUSE, 67235 BENFELD, FRANCE. Non contractual document.
ATyS p M – 542935E – SOCOMEC
Press for 3 s
To modify the
value of this
digit
To access the
other digits
Validate entry
2 phase / 3 wire
2 phase / 2 wire
1
L1
2NBL
2BL
2
L3
L2
NM
3
Browsing
1
2
1
2
1
2
1
2
1
2
Exit programming
Press the validate
button for
3 seconds.
SETTING RANGE
DEFAUT VALUE
0 to 60 sec (1)
3 sec
0 to 7200 sec
180 sec
0 to 60 sec
3 sec
0 to 3600 sec
5 sec
0 to 7200 sec
5 sec
0 to 600 sec
180 sec
0 to 20 sec
3 sec
SETTING RANGE
DEFAULT VALUE
AUTO
LEFT
AUTO
RIGHT
400Vac (230/400V version)
From 180 to 480 Vac
230Vac (127/230V version)
50 or 60Hz
50Hz
M-G
M-G
M-M
YES or NO
NO
3NBL / 4NBL / 41NBL /
1BL (230/400V version)
4NBL
4NBL / 3NBL / 2NBL /
42NBL (127/230V version)
1 phase / 2 wire
1
1
1BL
N
3
6A

Automatic operation

Close the front cover as
shown to put the product into
automatic mode.
6B

Manual operation

• Open the front cover as
shown to put into manual
mode.
• Use the handle situated in
the front panel under the cover to operate the
transfer switch.
• Check the changeover switch position on the
indicator before operating.
90º
90º
Extension
To simplify
operation use
the handle with
the extension
provided.
(Max 70.8 lb-in/8 Nm)
6C
Padlocking mode
• In order to padlock put the
product in manual mode.
• Pull the locking mecha nism
and insert a padlock as
shown.
• As standard padlocking in the 0 position.
Configurable to I-0-II (see step 1).
1x 4-8 mm
DE
11