The three selectors can be positioned in all the possible combinations since the respective
functions are independent from each other.
At each reactivation, the display shows the code corresponding to the setting of the internal selectors for
5 seconds:
D1
C0
J1
OFF
J2
OFF
J3
OFF

2.11.b - Presence contact input

To terminals "A" and "B" (fig. 20a-20b) it is possible to connect a free contact, not live, of a possible
presence sensor (not supplied) which, when closed, causes the deactivation of the appliance (factory
setting stand-by).
It is possible, in factory or an authorized assistance centre upon prior request of the customer, to change
this function so that the selected ambient temperature is automatically increased (in cooling mode) or
decreased (in heating mode) by a specific value "Economy Function" when the contact is closed.
To use this function, check that the terminals "A" and "B" are connected to the connector "X8".
It is not possible to connect the parallel input the one of other circuit boards;
use separate contacts.
To connect the presence sensor, it is necessary to use a double-insulated cable with a minimum section
of 2x0,5 mm
and maximum length of 20 m. Keep this connection separated from the power supply line
2
of the appliance.
2.12 - CONNECTION WITH WIRED REMOTE CONTROL B0736 OR THIRD PAR-
TIES MODBUS
- Set the connector on connection "X8" on the connector "X7".
The presence contact will be managed by the wall control B0736.
- Connect the cables coming from the connection "A B" of the control B0736 with the connector "A B" of
the control, taking care to respect the polarity, ending the farthest unit with the supplied 120 Ohm heating
element.
- Enable Remote configuration (paragraph "3.4", configuration parameter "CF").
- All the commands "
every time they are activated.
- The indicator "
and the set fan speeds.
- As regards the functionalities and settings, see the instructions of command B0736.
EN - 14
C1
C2
OFF
OFF
OFF
ON
ON
OFF
" shall be disabled and the message "rE" will appear on the display
" shows the chosen mode of operation, the indicators "
C3
C4
C5
OFF
ON
ON
ON
OFF
OFF
ON
OFF
ON
C6
C7
ON
ON
ON
ON
OFF
ON
", "
", "
" and "
"