Maintenance intervals
The tasks described below may only be carried
out by a qualified electrician.
Select the maintenance intervals with due consideration of
the following aspects:
„ Age and condition of the device
„ Environmental influences
„ Mechanical stress
„ Last test reports
Perform maintenance at least in the following intervals:
Component
Every 6 months
Electrical
Check residual current circuit breakers,
switching and
line circuit breakers, phase sequence
safety
relays, etc. for apparent defects.
devices
Check residual current circuit breaker
for damage.
Housing inte-
Check the fastening to the foundation.
rior
Tighten bolts as needed.
Housing exte-
Check device for defects or damage.
rior
Check cover lock for correct function-
ing. Clean, grease and adjust lock if
necessary.
Ensure that the device is clean. Clean
if necessary.
Î "8.2 Cleaning"
LED informa-
Check LED information panel for cor-
tion panel
rect functioning and readability.
Charging
Check hinged lid or shutter for correct
socket
functioning and ease of movement.
Check the contacts of the charging
socket for contamination and foreign
objects. If necessary clean charging
socket and remove foreign objects.
38
Maintenance work
Component
Yearly
Foundation
Check foundation.
Terminals
Check the terminals of the supply line.
If necessary retighten terminals.
Device
Repetition of measurements and tests
according to IEC 60364-6 and the
applicable national regulations (e.g. in
Germany: DIN VDE 0105-100).
f Eliminate damage to the device according to regula-
tions.
f Document maintenance sufficiently.
f If necessary, request a maintenance protocol from
MENNEKES.
Î "1.1 Service"

8.2 Cleaning

T
DANGER
Risk of fatalities due to electric shock
The device contains electrical components that carry high
voltage. Improper handling of the opened housing, espe-
cially in connection with moisture, will cause severe injury
to persons due to electric shock.
f Only clean the outside of the device.
f Keep the device and protective equipment closed.
Maintenance work