Installation and Start-up
1.7.4 Alarm Input
For a monitoring of the encoder to channel 1 and the encoder cable the signal tracks and the
zero track are monitored. If the connected encoder has no zero track, then the the 5V-supply
must be assigned to track N+ and COM to N- at the encoder plug. The monitoring for channel
1 will be switched on/off with parameter Ec.20 Bit 2.
The recognition of encoder breakage triggers an „error! Encoder 1" (value 32), if the voltage
between two signal pairs is smaller than 625mV.
2.
Installation and Start-up
2.1
Mechanical installation
All kind of works on the inverter may be carried out by authorized personnel in accordance
with the EMC and safety rules only.
• Switch inverter de-energized and await capacitor discharge time
• Pull off operator
• Remove plastic cover
• Remove fixing bolt
• Fix interface board beginning from the socket connector straightly
• Screw in fixing bolt
• Attach plastic cover
2.2
Electrical installation
Connection of the encoder cable
12
Motor encoder plug
�
�
�
�
�
��
��
�
��
�
�
�
���
��
�
���
�
��
�
���
�
��
�
���
�
���
��
���
��
Connect-up
external shield
at the respective
connector housing !
Socket X3A
5
4
3
2
1
10
9
8
7
6
15
14
13
12
11
���
Core color
�
��
�
���
�
��
�
���
�� ��
�� ���
�� ���
�� ���
green
yellow
blue
red
gray
pink
white
brown