Preconfiguring the Heat Pump Heating System

5 Preconfiguring the Heat Pump Heating System
The preconfiguration informs the controller about which
components are connected to the heat pump heating system.
Preconfiguration must be carried out before the system-specific
settings in order to show or hide menu items (dynamic menus).
The following table shows not only the menu structure and
explanations

5.1 Menu

You can access the preconfiguration menu by:
Simultaneously pressing (approx. 5 seconds) the button
combination (ESC) and (MENUE).
Exit the preconfiguration via the button (ESC).
The following presettings must be carried out:
Downloaded from
www.Manualslib.com
in
the
right-hand
column,
but
Preconfiguration of all system components for
dynamic menu structuring
Monovalent (heat pump as sole heat
generator), mono energy (heat pump and
immersion heater), bivalent-parallel (heat
pump and boiler), bivalent-alternative (heat
pump or boiler), bivalent-regenerative (heat
pump or reg. heat source)
Has an additional heat exchanger with
supplementary connections for DHW
preparation been installed in the heat pump?
Has the system got an unmixed heating circuit?
Has the system got a heating circuit 2 with a
controllable mixer?
Has the system got a heating circuit 3 with a
controllable mixer?
Will the cooling function of the reversible heat
pump be used?
Is a passive cooling controller connected to the
heating controller?
Is a 2 or a 4-pipe system used for passive
cooling?
Is DHW heating carried out by the heat pump?
manuals search engine
corresponding setting ranges. Values in bold print indicate the
factory settings.
The factory settings in the "Preconfiguration" menu correspond
to the integration diagram for a mono energy heat pump
(normally an air-to-water heat pump) with 1 compressor and a
also
the
heating circuit without DHW heating using the heat pump.
Abbreviations:
HP
Heat pump
AW HP
Air-to-water heat pump
BW HP
Brine-to-water heat pump
WW HP
Water-to-water heat pump
Setting range
Display
Monovalent
Bivalent-regenerative,
Mono energy
with nonreversible HP
only
Bivalent-parallel
Bivalent-alternat.
Bivalent-regener.
Yes
Reversible HP
No
AW HP
Yes
At all times
No
No
At all times
Yes
No
Heating circuit 2
Yes
Nonreversible HP
Nonbivalent system
Yes
Reversible HP
No
No
BW or WW HP
Yes
Nonreversible HP
2-pipe system
BW or WW HP
4-pipe system
Nonreversible HP
Passive cooling function
No
At all times
Yes
5.1
E-9