Level sensor Mono/Duo (non-ATEX)
Connect the cable ends of the level sensor to the terminals
(see "Fig. 3: Connecting the level sensor"). The connection
of level sensors is identical for both Mono and Duo systems.
Use KESSEL junction box (art. no. 28799) to lengthen the
connection cable of the level sensor.
Wire colour
Name on PCB
red
On/ON1
black
On/On1
Use KESSEL connection box (art. no. 28799) to lengthen
the connection cable of the level sensor.
4.5.1.2 Connecting diaphragm pressure switches
Diaphragm pressure switches for Mono systems
Connect the cable ends of the diaphragm pressure switches
to the terminals (see "Fig. 4: Diaphragm pressure switch
Mono ").
Wire colour
Name on PCB
yellow
Alarm
green
brown
ON
white
Diaphragm pressure switches for Duo systems
Connect the cable ends of the diaphragm pressure switches
to the terminals (see "Fig. 5: Diaphragm pressure switches
Duo").
Wire colour
Name on PCB
pink
Alarm
grey
yellow
On2
green
brown
On1
white
4.5.2
Install ATEX sensors
4.5.2.1 Connecting ATEX float switch
32 / 136
Terminal colour
white
blue
Terminal colour
white
blue
white
blue
Terminal colour
white
blue
white
blue
white
blue
Installation and operating manual
Mono
(+)
rt/RD
(-)
sw/BK
Fig. 3: Connecting the level sensor
Fig. 4: Diaphragm pressure switch Mono
Fig. 5: Diaphragm pressure switches Duo
Duo
(+)
rt/RD
(-)
sw/BK
Mono
yw
gn
bn
we
Duo
pk
gr
yw
gn
bn
we