Bus connection

6.1

Configuration

During the project planning of fieldbus devices, a physical
device is mapped as a modular system consisting of a
head module and multiple data modules. The device data
required for project planning is stored in GSD files
(General-Station-Description) in the GSDML format
(General Station Description Markup Language).
GSD file
The GSDML file for the BIS U-6028 can be downloaded on
the BALLUFF website.
The data modules of an IO device are represented in the
project planning software by slot. The GSDML file provides
the possible data modules (inputs or outputs of various
data width). For the configuration of an IO device, the
appropriate data modules are assigned to a particular slot.
Data modules
Input and output modules of 8 bytes, 16 bytes, 32 bytes,
64 bytes, 128 bytes and 254 bytes can be configured.
Integration in project planning software
The project planning is carried out using the project
planning tool SIMATIC NCM PC Manager or using STEP 7.
The following steps are required for integrating a processor
unit BIS U-6028:
1. Installing the GSDML file of the IO device in the
hardware configuration.
2. Updating the catalog.
3. Using "Insert object", add the IO device
"BIS U-6028_RT".
4. Insert the two modules for inputs and output (e.g.
"RT 32 Byte E" and "RT 32 Byte A" for the processor
unit "BIS U-6028_RT").
Additional project configuration settings:
5. The suffix "RT" provides visibility as to how the read
and write data are exchanged.
The processor unit includes a 2-port IRT switch
and thus is capable of passing through IRT data
packages.
The object properties of the module can be used to
configure the start addresses of the input and output data.
The input and output can be used to control the
BIS U-6028, as described in chapter Device
function on page 19.
14
english
6.2

Device name and IP address

6. The object properties of the inserted object "u-6028"
can be used to assign the device name, device number
and IP address.
The processor unit and the host system communicate via
the PROFINET protocol.
This means an IP address and a unique device name are
required. The device name and the IP address can be
stored in the IO device using "Target system > Ethernet >
Edit Ethernet node".
The processor unit BIS U-6028 is shipped
without a device name. The GSDML file has the
preset device name "u-6028".