2.2. Possible dangers at the installation location
DANGER Hot surfaces
The brass distributor/collector "Multidis
SFI" can get very hot during operation. Do
no touch without safety gloves.
The case of an external fire has not been taken into
consideration during design of the distributor/col-
lector.

3. Transport, packaging and storage

3.1. Transport inspection

Upon receipt, check delivery for any damages
caused during transit.
Any damages must be reported immediately upon
receipt.
3.2. Storage
The brass distributor/collector "Multidis SFI" must
only be stored under the following conditions:
• Do not store in open air, keep dry and free from
dust.
• Do not expose to aggressive fluids or heat
sources.
• Protect from direct sunlight and mechanical agi-
tation.
• Storage temperature: -20°C up to +55°C,
max. relative air humidity: 95
ATTENTION:
• Please protect against external forces (e.g.
impacts, vibrations etc.).
• External components such as handwheels,
pressure test points and actuators should
not be used as lever points during installa-
tion.
• Suitable means of transport and fitting de-
vices have to be used.

4. Technical data

4.1. Performance data

Max. operating pressure p
Max. differential pressure:
Max. operating temperature: 90°C
kvs value:
DANGER
Suitable measures (e.g. safety valves) have to
be taken so that the maximum operating pres-
sure and the maximum and minimum operating
temperatures are not exceeded or undercut.
8
: 6 bar (PN 6)
s
1 bar
2.4 m³/h
4.2. Dimensions / Connection dimensions
Illustr. 4.1: Dimensions brass distributor/collector
"Multidis SFI"
Item no.
Outlets
1414452
2
1414453
3
1414454
4
1414455
5
1414456
6
Illustr. 4.2: Lengths of brass distributor/collector
"Multidis SFI"
NOTE
The extension to a maximum of 20 circuits is
possible by connecting the distributor modules
NOTE
Determination of the total length of the distribu-
tor/ collector by adding the lengths of the dis-
tributor modules.

5. Construction and function

5.1. Summary
1. Flow distributor
2. Return collector
3. Ball valve
4. Regulating valve
5. Blind plug
6. Collar nut G2
7. Ring gasket
L
Length with
Length (L)
ball valves
1406586
180 mm
300 mm
260 mm
380 mm
340 mm
460 mm
420 mm
540 mm
500 mm
620 mm