Mounting and Connection Instructions DUO I/O-Module BUS-2/BUS-1
11.
Technical data
Rated operating voltage
Operating voltage range
Current consumption at U_b=12 V DC:
- Detector groups open
- Detector groups terminatd with 12k1
- LED indicator
- when cleared
4 detector group inputs with clear function
- Voltage
- Monitoring range
2 semiconductor outputs
Protection class as per DIN 40 050
Environmental class as per VdS
Operating temperature range
Storage temperature range
Installation module f.m.
Dimensions:
- Module s.m. (W x H x D)
- Module f.m.:
- Mounting dimensions (Æ x D)
- Mounting frame (W x H x D)
- Cover frame (W x H x D)
- 2-module cover frame (W x H x D)
Weight
010120.17
010130
Colour
1)
Depending on the control panel and the operating mode of the module, the monitoring range
is programmable (see 5.2.2)
12.
EN Conformity
Item no. 010120.17 as per EN 50131-3, Security grade 2, Environmental Class II
Item no. 010130
13.
Accessories for f.m. module
010123.17
2-module cover frame
010124.17
Decorating foil (PU = 5 pce.)
1)
as per EN 50131-3, Security grade 2, Environmental Class II
for DUO-/relay module (PU = 2 pce.)
12 V DC
9 V to 15 V DC
£ 5.0 mA
£ 0.6 mA in addition per detector group
£ 1.3 mA in addition per LED
no additional current consumption
8 V DC, stabilized, short-circuit protected
12k1 ± 20%
"open collector", LOW active,
max. 30 V DC, max. 50 mA per output
IP 40
II
-10 °C to +55 °C
-25 °C to +70 °C
Suitable for installating in flush mounted box with
Æ 60 mm (as per DIN or Austrian or Swiss flush
mounted box)
85 x 109 x 30 mm
58 x 26 mm
70 x 70 x 1 mm
80 x 80 x 5 mm
151 x 80 x 5 mm
41 g
116 g
Traffic white (similar to RAL 9016)