Herunterladen Inhalt Inhalt Diese Seite drucken

Connection Diagram; Overview; Detector Group Inputs; Semiconductor Outputs - Honeywell 010120.17 Montage, Anschluss, Anleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Mounting and Connection Instructions DUO I/O-Module BUS-2/BUS-1
9.

Connection diagram

9.1

Overview

Output 1
Output 2
Data
0 V
BUS-2/
BUS-1
+U_b
U_b
0 V
Shield
9.2

Detector group inputs

The terminal allocation of the 4 detector groups is identical
DG
0 V
Detector groups that are not being used require no end-of-line resistor if they are not assigned to
a function in the control panel.
9.3

Semiconductor outputs

ATTENTION: max. 50 mA per output
Consumer supplied with internal voltage
Consumer
Output 1
Output 2
LED2
0 V
+U_b
DIP switch
LED4
MC
GBS
1
2
Module
0 V
+12 V DC
vom BUS
LED1
LED3
Example:
Magnetic contact connection
GBS + MC
(MC) or glass breakage sensor
(GBS) in Z-wiring.
The integrated end-of-line resistor
can be used.
Combination GBS - MC
(First GBS, then MC)
End-of-line resistor R =12k1 at
3
end of line
Consumer supplied with external voltage
(max. 30 V DC)
Consumer
+U
Output 1
0 V
Output 2
21
Detector group 1
Detector group 2
Detector group 3
Detector group 4
1
2
3
.
A
Module
0 V
+12 V DC
from BUS