3 Installation
3.2 Fitting the device
3.2 Fitting the device
36
The latching function of the Q11 contactor relay prevents an automatic
restart.
The "remote reset"/"remote" function can be implemented by setting the
overload relay to AUTO.
▶
Mount the ZE/XTOM overload relay on the DIL(E)EM/XTMC contactor.
1.2 Nm
(10.6 lb-in)
PZ 2
Figure 7: Mounting DIL(E)EM/XTMC and ZE/XTOM
▶
Both can be mounted in any position, apart from as shown in figure 8.
Figure 8: Impermissible mounting positions for DIL(E)EM/XTMC and ZE/XTOM
(A1, A2 coil connection)
▶
Wire the motor cables.
1∼/⎓
3 ~
Figure 9: Main circuit wiring
ZE/XTOM 11/17 MN03407003Z-DE/EN www.eaton.com
A2
A1
≧ 5 mm (≧ 0.2")