2.3 Short-circuit protection of the overload relay

The short-circuit protection of the ZE/XTOM overload relay can be partially
implemented either with or without a fuse. The type of coordination is
related to the type of DILEEM or DILEM/XTMC contactor that is used
(→ table 2, page 28).
CAUTION
According to EN 60947-4-1 only type of coordination "2" may
be used for the protection of EEx e motors.
Table 3: Overview of short-circuit protection with ZE/XTOM relays
Type
ZE-0.16
XTOMP16AC1
ZE-0.24
XTOMP24AC1
ZE-0.4
XTOMP40AC1
ZE-0.6
XTOMP60AC1
ZE-1.0
XTOM001AC1
ZE-1.6
XTOM1P6AC1
ZE-2.4
XTOM2P4AC1
ZE-4
XTOM004AC1
ZE-6
XTOM006AC1
ZE-9
XTOM009AC1
ZE-12
XTOM012AC1
1) According to IEC/EN 60947
ZE/XTOM 11/17 MN03407003Z-DE/EN www.eaton.com
2.3 Short-circuit protection of the overload relay
Short-circuit
With fusing
current rating
Type of coordination
I
q
1)
„1"
kA
A gG/gL
100
20
100
20
100
20
100
20
100
20
100
20
100
20
100
35
100
35
100
35
100
35
2 Engineering
1)
„2"
A gG/gL
0.5
1
2
2
4
6
6
20
20
20
20
33