8.2.4

Outputs

Figure 8: Pull-out 6-pole terminal board: example of output connection

With reference to Figure 8 the digital outputs available are:
Output
Terminal no.
1
OUT1
2
3
4
OUT2
5
6
The outputs OUT1 and OUT2 are available on the pull-out 6-pole terminal board as specified in Table 5
which also shows the type of contact (NC = Normally Closed, COM = Common, NO = Normally Open).
The electrical characteristics of the contacts are shown in Table 6.
In the example shown in Figure 8 the light L1 is lit when there is an alarm in the system and it goes off when
no kind of malfunction is found, whereas the light L2 is lit when the pump is running and goes off when the
pump is stopped.
Max. bearable voltage [V]
Max. bearable current [A]
Max. accepted cable section [mm²]
ENGLISH
Type of contact
NC
COM
NO
NC
COM
NO

Table 5: Outputs OUT1 and OUT2

Characteristics of the output contacts

Table 6: Characteristics of the output contacts

Associated function
Presence/Absence of alarms in the system
Pump running/Pump stopped
250
5
If resistive load
2.5
If inductive load
2.5
35