When finishing the connection and pressurization operations of the hydraulic
1
system, execute a tightness test at a higher pressure than the standard one, in
order to avoid water leaks during the regular use of the unit.
2
MAX. TIGHTENING TORQUE FOR THE CONNECTION OF THE YORK VALVE
KIT IS 20 Nm
3
If the control valves are not supplied by YORK, YORK is not responsible for any mal-
4
function or wrong electrical connection referred to the valves.

6.6 ELECTRICAL CONNECTIONS

5
Before making any electrical connection, verify the compatibility between power supply
and the technical features of the fan coil and/or of the other accessories to be connected
6
to the unit. These features are illustrated in the identification plate, located on one side of
the fan coil (Fig. 1).
7
In the power supply system to the fan coil, a double-pole switch must be fore-
seen with a minimum distance of 3 mm between contacts in each poles.
8
For a correct management and use of the fan coil, the use of an YORK microprocessor
control is suggested. The control has to be chosen according to the requirements of the
installation.
9
In standard configurations (for example CBL00-Encl.3/A) it is not possible to
connect more than one motor in parallel to the same speed selector or ther-
10
moregulator. For this requirement, a special optional card and the relevant elec-
tric diagram are necessary.
+
Each fan coil is provided with:
screw terminal board for the electrical connections, indicated inside the CBL00 control
box (s. Enclosure 4 - Fig. 1);
electric wiring diagram, specific for the working of the unit and its accessories, located
in the front inner part of the unit;
ground protection terminal marked with the symbol
ground protection system cable (yellow/green).
To connect the fan coil unit to the electric system, operate as follows:
1. Insert the wires (factory pre-wired cable) through the slots in the base of the control box