• Insulation class: I.
• Protection grade: IPX0.
• Technical features of the heat exchanger:
-
Max pressure of the hot or cold water for water fan coil:
1600 kPa - with valves: 1000 kPa.
-
Min pressure of the hot or cold fluid: It is the one indicated by the designer/installer for
the correct functioning of the system.
-
Min/max water temperature: 5/85 °C.
-
Hardness of water into the heat exchanger: It is the one indicated by the de-
signer/installer for the correct functioning of the system.
-
Max pressure of the refrigerant fluid for units with direct expansion coil: 2400 kPa
• Technical features of the fan motor:
-
With each fan coil unit there is the possibility to have 6 different air volumes and
the relevant electric motor connections accordingly to the use requirements. The
standard electrical connection has a triad of speeds: MIN-MED-MAX (L-5, L-3,
L-2). The relevant nominal air capacities are indicated in the Encl. 3 and they are
referred to standard fan coil units, with clean filters, at the temperature of 20 °C,
at sea level and without external static pressure.
-
The electric motor is provided with internal thermic protection; it is a monophasic
motor with capacitor permanently inserted.

5. TRANSPORT AND WAREHOUSE STORAGE

All fan coils with casing are wrapped in a plastic bag to protect the unit from dust and scratches;
they are then packed in a cardboard box to allow an easy and safe manoeuvrability and to
minimise risks due to incorrect handling.
Fan coil units without casing are directly packed in a carton box.
On the carton box, symbols showing how to stock the goods correctly are printed. A label on it
provides complete information on its contents.
If fan coils are stored in the warehouse, do not exceed the following stacking limitations:
• MODELS WITH CASING:
Stacking position: VERTICAL;
Max. no. of units that may be stacked: 3.
• MODELS WITHOUT CASING (CONCEALED MODELS)
Stacking position: HORIZONTAL;
Max. no. of units that may be stacked: 7
Even though the units have been properly protected to withstand adverse conditions,
we recommend that they be kept under the following ambient conditions if stored in the
EN