IEC 61850 Ed.1 Client PIXIT
Description
Which status value (ST) quality bits are used in the client
Describe how to view/display quality values
Describe how to view/display time quality process values
from the server
Describe how to force a SetDataValues request
Describe how to force a GetAllDataValues request
Describe how the client behaves in case of:
GetDataDefinition response-
GetLogicalDeviceDirectory response-
GetAllDataValues response-
GetDataValues response-
SetDataValues response-
PIXIT for Reporting model
Description
Does the client search for RCB in all logical nodes? When not
specify the logical nodes
Which dynamic RCB attributes are/can be configured by the client
Does the client supports IED's with indexed and non-
indexed report control blocks (RCB)
The supported trigger conditions are
ME-RTU Remote Terminal Unit
Value / Clarification
Y
Good,
Y
Invalid,
N
Reserved,
Y
Questionable
Y
BadReference (used for analog statuses only)
N
Oscillatory
N
Failure
N
OldData
N
Inconsistent
N
Inaccurate
Y
Process
Y
Substituted
N
Test
Y
OperatorBlocked
Original Quality values could be seen only on debug screen.
Translated Quality values are sent to IEC 60870-5-104 Con-
trol Station (master)
N
LeapSecondsKnown
N
ClockFailure
N
ClockNotSynchronized
(displayed only in debug screen)
Used for SPG, ING, ASG.
SetDataValues are set by IEC 60870-5-104 commands.
Not supported
Client continues normal operation
Value / Clarification
The following logical nodes: LLN0
RptID
DataSet
Optional fields
Trigger conditions
Buffer time
Integrity period
Buffered RCB indexed
Buffered RCB not indexed
Unbuffered RCB indexed
Unbuffered RCB not indexed
integrity
data change
quality change
data update
general interrogation
(conditions are not evaluated)
N
N
Y
N
N
N
Y
Y
Y
Y
Y
Y
Y
Y
Y
E - 3