IMPLEMENTATION TABLE
3
IMPLEMENTATION TABLE
The following implementation table identifies which object groups and variations, function codes
and qualifiers the device supports in both requests and responses. The Request columns identify all
requests that may be sent by a Master, or all requests that must be parsed by an Outstation. The
Response columns identify all responses that must be parsed by a Master, or all responses that may be
sent by an Outstation.
NOTE
The implementation table must list all functionality required by the device whether Master or Out-
station as defined within the DNP3 IED Conformance Test Procedures. Any functionality beyond
the highest subset level supported is indicated by highlighted rows. Any Object Groups not pro-
vided by an outstation or not processed by a Master are indicated by strikethrough (note these
Object Groups will still be parsed).
OBJECT GROUP & VARIATION
Object
Number
0
0
0
0
0
0
0
0
1
1
1
2
2
2
2
3
ME-RTU Remote Terminal Unit
Variation
Description
Number
Device Attributes –
Device manufac-
242
turer's software
version
Device Attributes –
Device manufac-
243
turer's hardware
version
Device Attributes –
246
User assigned ID
code/number
Device Attributes –
248
Device serial number 1
Device Attributes –
Device manufac-
250
turer's product
name and model
Device Attributes –
252
Device manufac-
turer's name
Device Attributes –
254
None-specific all
attributes request
Device Attributes –
255
List of attribute
variations
Binary Input –
0
Any Variation
Binary Input –
1
Packed format
Binary Input –
2
With flags
Binary Input Event
0
– Any Variation
Binary Input Event
1
– Without time
Binary Input Event –
2
With absolute time
Binary Input Event
3
– With relative time
Double-bit Binary
0
Input – Any
Variation
REQUEST
Outstation parses
Function Codes
Qualifier Codes
(dec)
(hex)
1
(read)
00 (start-stop)
1
(read)
00 (start-stop)
1
(read)
00 (start-stop)
(read)
00 (start-stop)
1
(read)
00 (start-stop)
1
(read)
00 (start-stop)
00 (start-stop)
1
(read)
06 (no range, or all)
00 (start-stop)
1
(read)
06 (no range, or all)
00, 01 (start-stop)
1
(read)
06 (no range, or all)
22 (assign class)
07, 08 (limited qty)
17, 27, 28 (index)
00, 01 (start-stop)
06 (no range, or all)
1
(read)
07, 08 (limited qty)
17, 27, 28 (index)
00, 01 (start-stop)
06 (no range, or all)
1
(read)
07, 08 (limited qty)
17, 27, 28 (index)
06 (no range, or all)
1
(read)
07, 08 (limited qty)
06 (no range, or all)
1
(read)
07, 08 (limited qty)
06 (no range, or all)
1
(read)
07, 08 (limited qty)
06 (no range, or all)
1
(read)
07, 08 (limited qty)
00, 01 (start-stop)
1
(read)
06 (no range, or all)
22 (assign class)
07, 08 (limited qty)
17, 27, 28 (index)
RESPONSE
Outstation can issue
Function Codes
Qualifier Codes
(dec)
(hex)
00 (start-stop)
129 (response)
17 (index)
00 (start-stop)
129 (response)
17 (index)
00 (start-stop)
129 (response)
17 (index)
00 (start-stop)
129 (response)
17 (index)
00 (start-stop)
129 (response)
17 (index)
00 (start-stop)
129 (response)
17 (index)
00 (start-stop)
129 (response)
5B (free format)
00, 01 (start-stop)
129 (response)
17, 28 (index)
00, 01 (start-stop)
129 (response)
17, 28 (index)
129 (response)
17, 28(index)
130 (unsol. resp)
129 (response)
17, 28 (index)
130 (unsol. resp)
129 (response)
17, 28 (index)
130 (unsol. resp)
A - 47