Introduction
This document specifies the protocol implementation extra information for testing (PIXIT) of the IEC 61850
interface in the client system: "ME-RTU" with firmware version "90.34", further referred to as "client".
Together with the PICS and the MICS the PIXIT forms the basis for a conformance test according to
IEC 61850-10.
The following chapters specify the PIXIT for each applicable ACSI service model as structured in
IEC 61850-10 and the "Conformance Test Procedures for Client System with IEC 61850-8-1 interface".
PIXIT for Configuration
Description
Describe how the client handles nameplate configuration
revision mismatches
Describe how the client handles report control block config-
uration revision mismatches
PIXIT for Association model
Description
Guaranteed number of servers that can set-up an associa-
tion simultaneously (one association per server)
Lost connection detection time range (default range of
TCP_KEEPALIVE is 1 – 20 seconds)
Lost (abort) connection retry time
What is the maximum and minimum MMS PDU size
What is the typical startup time after a power supply interrupt 1 minute
PIXIT for Server model
Description
Maximum object identification length
Does client support auto description
What analogue value (MX) quality bits are used in the client
E - 2
IEC 61850 Ed.1 Client PIXIT
Value / Clarification
Don't care about nameplate
All mismatches except Report revision are ignored
Value / Clarification
32
Keepalive parameters are settable by OS settings. Recom-
mend timeout is 10s
20 seconds
Max MMS PDU size : 65000
Min MMS PDU size : /
Value / Clarification
64
No
Y
Good,
Y
Invalid,
N
Reserved,
Y
Questionable
Y
Overflow
N
OutofRange
N
BadReference
N
Oscillatory
N
Failure
N
OldData
N
Inconsistent
N
Inaccurate
Y
Process
Y
Substituted
N
Test
Y
OperatorBlocked

Werbung