Pos: 11.4 /Elektrischer Anschluss/Temperatur/TTR200/Hinweis zu Leitungsmaterial TTR200 @ 15\mod_1195568460984_3101.doc @ 141814
4.1

Conductor material

Standard conductor material must be used for the power supply cable.
The maximum connectable conductor cross-section amounts to 2.5 mm
Notice - Potential damage to parts!
A rigid conductor material can result in wire breaks.
The connecting cable must be flexible.
Pos: 11.5 /==== Leeres Modul mit einer Absatzmarke, IM, 1-spaltig ==== @ 14\mod_1194422545687_0.doc @ 136717
Pos: 11.6 /Überschriften/1.1/1-spaltig/A - C/Anschlussbelegung @ 16\mod_1199260233671_3101.doc @ 146854
4.2

Pin configuration

Pos: 11.7 /Überschriften/1.1.1/1-spaltig/Versorgungs- / Sensoranschluss @ 16\mod_1199260387640_3101.doc @ 146877
4.2.1

Supply voltage / sensor connection

Pos: 11.8 /Elektrischer Anschluss/Temperatur/TTR200/Anschlussplan (BA) @ 18\mod_1203682458036_3101.doc @ 164662
Fig. 2: *(planned local configuration interface/inoperable)
1
Potentiometer: 0 ... 500 Ω or 0 ... 5000 Ω
a
Potentiometer, 2-wire circuit
b
Potentiometer, 3-wire circuit
c
Potentiometer, 4-wire circuit
2
RTD resistance sensors (e.g., Pt100)
d
RTD, 2-wire circuit
e
RTD, 3-wire circuit
f
RTD, 4-wire circuit
Pos: 11.9 /Elektrischer Anschluss/Temperatur/TTR200/Anmerkung zu Anschlussplan (CI) @ 18\mod_1205828231074_3101.doc @ 171016
Note
Terminal 11: Measurement of 4 ... 20 mA output current without opening / interrupting the current loop.
PWR / green LED: Supply voltage display
ERR / red LED: sensor, sensor lead & unit fault signaling
DIP switch 1:
on -> Hardware write protection is enabled
DIP switch 2:
no function
Pos: 11.10 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
CI/TTR200-X1
3
Thermocouple
Depending on the sensor model, a variety of line materials can be used
for sensor connections. The integrated reference point makes it possible
to directly connect thermal compensating lines.
4
Voltage measurement
TTR200
Electrical connection
2
.
EN - 7