Herunterladen Inhalt Inhalt Diese Seite drucken

Daikin EWWD370H-XS Bedienungsanleitung Seite 11

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 18
70
65
60
55
50
45
40
35
30
25
20
15
10
5
0
-10
Safety
The machine must be firmly secured to the ground.
It is essential to observe the following instructions:
- The machine must be raised only by the lifting points. Only
these points can support the whole weight of the unit.
- Do not allow unauthorised and/or unqualified personnel to
access the machine.
- It is forbidden to access the electrical components without
having opened the machine's general disconnecting switch
and switched off the power supply.
- It is forbidden to access the electrical components without
using an insulating platform. Do not access the electrical
components if water and/or moisture are present.
- All operations on the refrigerant circuit and on components
under pressure must be carried out by qualified personnel
only.
- Replacement of a compressor or addition of lubricating oil
must be carried out by qualified personnel only.
- Sharp edges can cause wounds. Avoid direct contact.
- Avoid introducing solid bodies into the water pipes while the
machine is connected to the system.
- A mechanical filter must be installed on the water pipe
connected to the heat exchanger inlet.
- The unit is supplied with a single pole high pressure safety
switch that opens when the pressure exceeds the limit. When
the switch opens the control relay is switched off by turning off
the compressor. The pressure switch is mounted on the
compressor discharge port.
In case of cut out, reset the switch by pressing the blue button
and then reset the alarm on the microprocessor.
- The unit is supplied with safety valves also, that are installed
on both the high and the low pressure sides of the refrigerant
circuit.
- Install in the line connecting the discharge of safety valves
leak refrigerant sensor.
It is absolutely forbidden to remove all protections of
moving parts.
Figure 2 - OPERATION RANGE
Operation with glycol
-5
0
Evaporator Leaving Water Temp. (°C)
Unit with option
'high temperature kit'
Standard unit
Part Load Operation only
5
10
In case of sudden stop of the unit, follow the instructions on the
Control Panel Operating Manual which is part of the on-
board documentation delivered to the end user.
It is strongly recommended to perform installation and
maintenance with other people. In case of accidental injury or
unease, it is necessary to:
-
keep calm
-
press the alarm button if present in the installation site
-
move the injured person in a warm place far from the unit
and in rest position
-
contact immediately emergency rescue personnel of the
building or the Health Emergency Service
wait without leaving the injured person alone until the
-
rescue operators come.
Moving and lifting
Avoid bumping and/or jolting during loading/unloading unit
from the truck and moving it. Do not push or pull the unit from
any part other than the basis. Secure the unit inside the truck
to prevent it from moving and causing damages. Do not allow
any part of the unit to fall during transportation or
loading/unloading.
Use extreme caution when handling the unit to prevent
damage to the control or the refrigerant piping. The unit must
be lifted by inserting a hook in each corner, where there are
holes for lifting (see fig. 3). Spacer bars must be used along
the line connecting the lifting holes to prevent damage to the
electric panel and motor terminal box. During the lifting phase
to verify that the ropes and / or the lifting chains do not touch
the electrical panel and / or piping. If moving the machine, you
had the sleds or skates, push only on the basis of the machine
without touching the pipes of copper, steel, compressors and /
or the electrical panel.
Both the lifting ropes and the spacing bars must be
strong enough to support the unit safely. Please check
the unit's weight on the unit nameplate.
D-EIMWC00308-16EU - 11/192
15
20

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Ewwdc12h-xs

Inhaltsverzeichnis