Function
Control unit TCG 1xx

Standard function with leakage test

Symbol
Standard function
Functional sequence phases:
1 : No voltage.
2 : Power supply on, no heat request.
3 : Heat request, check air pressure switch idle
position.
4 : Motor on, check air pressure.
5 : First phase sealing test
Pressing and
holding the R button
... leads to ...
for...
Unlocking of the
... 1 second ...
control unit
Locking of the
... 5 seconds ...
control unit
Clearance of control
... 9 seconds ...
unit statistics
A4
Display
BP1 push-button 1
Request: fault code
BP2 push-button 2
Request: values
Designation
Waiting for heat request
Valve leak check
(by gas pressure measurement in valve
space)
Waiting for air pressure switch during
burner start
Burner motor on
Ignition transformer on
Flame present
(valve space depressurised).
6 : Test time 1
7 : Valve check second phase (valve space filled).
8 : Test time 2.
9 : Preventilation.
9': Pre-ignition, activation of unauthorised
flame monitoring.
05/2014 - Art. Nr. 420010540302
The TCG 1xx automatic gas combustion
control unit controls and monitors the
forceddraught burner.
The microprocessorcontrolled programme
sequence ensures maximum stability of time
periods, regardless of fluctuations in the
power supply or ambient temperature. The
automatic combustion control unit is
designed to cope with brownouts,
guaranteeing system operation even in the
event of extreme power failures. Whenever
the supply voltage drops below its rated
minimum level, the control unit shuts down -
even in the absence of a malfunction signal.
The control unit switches itself back on
again once the voltage has returned to
normal levels.
Locking and unlocking the system
The control unit can be locked (switched to
malfunction) and unlocked (malfunction
cleared) by pressing the R reset button,
provided the system is connected to the
mains power supply. If the button is pressed
during normal operation or start-up, the unit
enters malfunction mode. If the button is
pressed in malfunction mode following a
safety shutdown, the control unit is
unlocked.
Always disconnect the power supply
before installing or removing the
control unit. Do not attempt to open or
carry out repairs on the control unit.
10 : Flame formation, safety period
11 : Post-ignition time
12 : Operation
13 : Burner stop
14 : Postventilation
14' : Continuous motor operation
15 : Standby