Herunterladen Inhalt Inhalt Diese Seite drucken

Standard Function Without Leakage Test - elco CB-P2.170 G-U/TCG KN Betriebsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
Function
Control unit TCG 1xx

Standard function without leakage test

Symbol
Standard function
Functional sequence phases:
1 : No voltage.
2 : No heat request when the power is on.
3 : Heat request, checking rest status of the air
pressure switch.
4 : Motor powered, air pressure check.
68
Pressing and
holding the R button
... leads to ...
for...
Unlocking of the
... 1 second ...
control unit
Locking of the
... 2 seconds ...
control unit
Clearance of control
... 9 seconds ...
unit statistics
A4
Display
BP1 push-button 1
Request: fault code
BP2 push-button 2
Request: values
Designation
Waiting for heat request
Waiting for air pressure switch during
burner start
Burner motor on
Ignition transformer on
Flame present
5 : Pre-ventilation
5' : Pre-ignition, activation of unauthorised flame
monitoring.
6 : Flame formation, safety time
7 : Post-ignition time
8 : Operation
05/2014 - Art. Nr. 420010540302
The TCG 1xx automatic gas combustion
control unit controls and monitors the
forceddraught burner.
The microprocessorcontrolled programme
sequence ensures maximum stability of time
periods, regardless of fluctuations in the
power supply or ambient temperature. The
automatic combustion control unit is
designed to cope with brownouts,
guaranteeing system operation even in the
event of extreme power failures. Whenever
the supply voltage drops below its rated
minimum level, the control unit shuts down -
even in the absence of a malfunction signal.
The control unit switches itself back on
again once the voltage has returned to
normal levels.
Locking and unlocking the system
The control unit can be locked (switched to
malfunction) and unlocked (malfunction
cleared) by pressing the R reset button,
provided the system is connected to the
mains power supply.
Always disconnect the power supply
before installing or removing the
control unit. Do not attempt to open or
carry out repairs on the control unit.
9 : Burner shutdown
10 : Regulator shutdown

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Cb-p2.170 g-u/tcg klCb-p2.170 g-u/tcg/tc knCb-p2.250 g-u/tcg knCb-p2.250 g-u/tcg klCb-p2.250 g-u/tcg/tc knCb-p2.250 g-u/tcg/tc kl

Inhaltsverzeichnis