Assembly
Burner assembly
Gas connection
Gas lines
When installing the gas lines and gas train,
the general EN676 directives and guidelines
must be observed.
EN676 compulsory kit and accessories in
order to comply to the safety regulations.
Additional accessories and kits shall be
installed by the installer in accordance to the
local safety regulations and codes of
practise.
General regulations applying to the gas
connection
• The gas train must only be connected to
the gas mains by a recognised specialist.
• The cross-section of the gas line should be
of a size designed to guarantee that the
gas flow pressure does not drop below the
specified level.
• A manual shut-off valve (not supplied) must
be fitted upstream of the gas train.
• In Germany, a thermally triggered shut-off
LEGENDA
Pf: Back pressure of furnace
Pb: Pressure of burner (combustion head +
complete gas train)
Pin: Minimum inlet pressure
74
5
4
3
valve (to be installed by the customer side)
must be fitted as specified by the draft
combustion ordinance. It is the
responsibility of the fitter or his
representative to obtain approval for the
system at the same time as the burner is
commissioned. Only the fitter or his
representative can guarantee that the
system meets applicable standards and
regulations. The fitter should be in
possession of the corresponding official
permit, and should carry out the
corresponding sealing tests and purge the
system of air.
05/2014 - Art. Nr. 420010540302
Burner assembly
The burner is fixed by mean of connecting
flange and therefore to the boiler.
Installation:
• fix the flange 3 to the boiler with
the screws 4
• turn the burner slightly, guide it into
the flange and secure using screw 5
Removal:
• loosen screw 5
• turn the burner out and pull it out of
the flange.
Burner blast tube insertion depth and
brickwork
Unless otherwise specified by the boiler
manufacturer, heat generators without a
cooled front wall require brickwork or
insulation 5 as shown in the illustration.
The brickwork must not protrude beyond
the leading edge of the blast tube, and
should have a minimum conical angle of
60°. Gap 6 must be filled with an elastic,
non-combustible insulation material. For
boilers with reverse firing, the minimum
burner tube insertion depth A as speci fied in
the boiler manufacturer's instructions must
be observed.
Exhaust system
To avoid unfavourable noise emissions,
right-angled connectors should not be
used on the flue gas side of the boiler.