Drain Piping

CAUTION
Following the Installation Manual, perform the drain piping work so that water is properly drained. Apply a heat
insulation so as not to cause a dew condensation.
Inappropriate piping work may result in water leakage in the room and wet furniture.
• Provide the indoor drain piping with proper heat insulation.
• Provide the area where the pipe connects to the indoor unit with proper heat insulation. Improper heat insulation
will cause condensation to form.
• The drain pipe must be sloping downward (at an angle of 1/100 or more), and do not run the pipe up and down
(arched shape) or allow it to form traps. Doing so may cause abnormal sounds.
• Restrict the length of the traversing drain pipe to 20 meters or less. For a long pipe, provide support brackets at
intervals of 1.5 to 2 meters to prevent flapping.
• Install the collective piping as shown in the following figure.
• Do not provide any air vents. Otherwise, the drain water will spout, causing water to leak.
• Do not allow any force to be applied to the connection area with the drain pipe.
Support
1.5 m to 2 m
bracket
(Collective
piping)
Heat
insulator
Downward slope
1/100 or more
 Installation of accessories
Install the drain pan (accessory) on the pipe side of the indoor unit.
Drain pan screw
(accessory)
Drain pan (accessory)
97-EN
As long as possible
(Approx. 10 cm)
Downward slope
1/100 or more
VP30
Incorrect
Cut the insulation, insert the protrusion on the drain pan into the hole, and then
install it by pushing it in the directions indicated by the arrows.
– 49 –
 Pipe material, size and insulator
The following materials for piping work and insulating process are procured locally.
Pipe material
Insulator
Drain hose
Use adhesive for PVC pipe
Elbow
 Connecting drain pipe
Insert the drain hose into the connector until the hose can go no farther.
Arched shape
REQUIREMENT
• Connect the hard vinyl chloride pipes certainly so that water does not leak by using adhesive agent for vinyl chloride.
• It takes some time to dry and indurate the adhesive agent. (Refer to the manual of adhesive agent.) Do not apply any
extra force on the connecting section until the adhesive agent dried.
Trap
CAUTION
Sometimes, debris will accumulate in the drain pan while installation work is in progress. Remove the drain filter from
the drain pan and clean it.
After cleaning the drain filter, replace it in the drain pan.
 Check the draining
Pour water to the drain pan. Confirm that water drains well and does not leak from the drain hose connecting part.
PVC pipe, pipe elbow (Nominal outer diameter Ø20 mm)
Foamed polyethylene foam, thickness: 10 mm or more
Drain pan
PVC pipe
Insulation
Drain filter
98-EN