Additional refrigerant charge
9.3 ADDITIONAL REFRIGERANT CHARGE CALCULATION
Although refrigerant has been charged into this unit in advance, additional refrigerant charge is required according to piping length.
Determine the additional refrigerant quantity according to the following procedure, and charge the system with it.
Record the additional refrigerant quantity to facilitate maintenance and servicing activities thereafter.
Calculating method of additional refrigerant charge (W kg)
No.
Symbol
Pipe diameter (mm)
∅19.05
∅15.88
1
W1
N O T E
In the case that the quantity calculated above is less than the minimum quantity indicated in the table below, adopt
the quantity in the table below as the additional refrigerant quantity for piping liquid, regardless of the piping length.
HP
Minimum additional charge of base unit (kg)
For combination of the units, adopt the total minimum quantity of each base unit as the minimum additional refriger-
ant quantity.
Additional refrigerant charge quantity for indoor unit (only for heat pump system) (W2 kg)
The additional refrigerant charge is required depending on the number of connected indoor units. Select the refriger-
ant quantity from the following table.
Additional refrigerant charge quantity (kg)
2
W2
Connectable
number
Additional refrigerant charge calculation for indoor unit (W3 kg)
Additional refrigerant charge is 1kg/unit of 8HP and 10HP indoor unit.
3
W3
Additional refrigerant charge of less than 8HP indoor units is not needed.
8 and 10HP Total Indoor Unit Numbers
The ratio of indoor unit connection capacity (indoor unit total capacity/outdoor unit capacity) additional charge
(W4 kg).
Determine the ratio of indoor unit connection capacity.
4
W4
Condition
I.U. Capacity Ratio is less than 100%:
I.U. Capacity Ratio is more than 100%:
5
W
Calculation of additional charge (W kg) = W1 + W2 + W3 +W4
51
PMML0294A_rev.2_02-2014.indb 51
Additional refrigerant charge calculation for liquid piping (W1 kg)
Total piping length (m)
∅22.2
m
m
m
∅12.7
m
m
∅9.52
m
∅6.35
System
Model
RCI-2.0FSN3
1
0.0
2
0.5
3
0.5
4 or more
1.0
PMML0294A rev.2 - 07/2014
Contents
Refrigerant amount for 1m pipe
(kg/m)
× 0.36 =
× 0.26 =
× 0.17 =
× 0.11 =
× 0.056 =
× 0.024 =
Total additional charge for liquid piping =
5
6
2.0
2.0
Heat Pump
RCI-2.5FSN3
RCI-3.0-6.0FSN3
0.0
0.5
0.5
1.0
1.0
1.5
1.5
2.0
Additional Charge
× 1.0kg/unit =
Refrigerant amount
0.0kg
0.5kg
Additional charge
(kg)
8
10
12
14
16
2.0
2.0
3.0
3.0
3.0

Heat Recovery

RCI-2.0-6.0FSN3
0.0
0.0
0.0
0.0
Additional
charge (kg)
kg
kg
kg
kg
kg