2. Installation

Install the charger vertically on a non-combustible surface with the
supply terminal facing down. To optimise cooling, maintain a minimum
distance of 10 cm below and above the product.
Install close to the battery, but never immediately above the battery (to
prevent damage due to gas formation by the battery).
Use flexible multi-core copper cables for the connections: see safety
instructions.
Poor internal temperature compensation (e.g. ambient conditions of
battery and charger not within 5°C) may shorten the life span of the
battery.