B

Mains connection

Danger!
Switch off power supply
Dangerous voltage: The power terminals may carry dangerous voltages for some time even if
the power supply is switched off. Wait for some minutes before starting to work at the
frequency inverter.
Make sure that the frequency inverter is de- energized.
Do not carry out high voltage insulation tests on cable connect to the frequency inverter.
Follow local wiring codes
Connect mains supply.
Type
3~400 V
kW
F1
A
L1, L2, L3
2
mm
PE
2
mm
or
Type
3~230 V
kW
0.18...0.75
F1
A
L1, L2, L3
2
mm
PE
2
mm
or
Type
1~230 V
kW
0.09...0.37
F1
A
L1, N
2
mm
PE
2
mm
or
Agile
Quick Start Guide
-02...-11
-13
0.25...1.5
2.2
6
10
1.5
2 x 1.5
1 x 10
-01...-07
-09
1.1
6
10
1.5
2 x 1.5
1 x 10
-01...-07
-09
0.55
6
10
1,5
2 x 1,5
1 x 10
Note:
0,5
Nm
mm
AWG
-15
-18
-19
3.0
4.0
5.5
10
10
16
-11...-13
-15
1.5...2.2
3.0
16
25
-11...-13
-15
0.75...1.1
1.5
16
25
2,5
2 x 2,5
1 x 10
32
Only required for DC-
link connection.
2
1,5
2,5
4
16
14
12
AWG: American Wire Gauge
(American unit)
-21
-22
-23
7.5
9.2
11
25
35
35
2.5
2 x 2.5
2 x 4
1 x 10
1 x 10
-18
-19
4.0
5.5
35
35
2.5
4
2 x 2.5
2 x 4
1 x 10
1 x 10
-18
-19
2.2
3.0
35
35
4
2 x 4
1 x 10
05/2013
10
8
4
-21
7.5
50
6
2 x 6
1x10
-21
3.0

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Vectron agile agl402

Inhaltsverzeichnis