Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Data; Scope Of Delivery; Description And Function; Installation And Electrical Connection - Wilo -E series Einbau- Und Betriebsanleitung

Elektronische pumpe mit asynchronmotor
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 16

5.2 Technical data

Connected voltage
Protection class IP
Water temperatures
Max. operating pressure
Max. ambient temperature
Min. inlet pressure
5.3

Scope of delivery

• Circulation pump complete
• Installation and operating instructions

6 Description and function

The pump (fig. 1) consists of a hydraulic system, a glandless
pump motor an electronic control module. The control module
includes a red button for setting all parameters.

7 Installation and electrical connection

Installation and electrical connection must be carried out in
accordance with local regulations and only by qualified per-
sonnel!
WARNING! Risk of personal injury!
The existing directives for accident prevention must be
adhered to.
DANGER! Danger of electric shock!
Danger from electrical current must be eliminated.
Local directives or general directives [e.g. IEC, VDE etc.] and
local power supply companies must be adhered to.
Installation and operating instructions Wilo E.../1-5
1~230 V +10 %/-15 %, 50 Hz ±5 %
44 (acc. fig. 3)
+ 10°C to + 95°C
10 bar
+ 60°C
0.05 bar at 50°C / 0.3 bar at 95°C
English
8

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis