2.3
Wiring Example with Intrinsically Safe Supply Unit
Fig. 3
Wiring example
2.4
Grounding and Potential Equalization
The EE100Ex must be integrated into the potential equalization in order to avoid hazards from
electrostatic charges. The standards EN60079-14, EN60079-25 or IEC60079-14, IEC60079-25
must be observed.
The cross-section of the grounding conductor or of the potential equalization connection must be
min 4 mm² (0.06 sq.in). The EE100Ex features a grounding port on the exterior of the enclosure.
With stranded wires, the cable ends should be fitted with suitable wire-end sleeves.
The resistance of the ground connection of the intrinsically safe barrier must be max. 1 ohm.
Fig. 4
Grounding and potential equalization
8
hazardous area
Systemground
non-hazardous area
intrinsically safe
supply unit
CH2
+
+
CH2
-
-
CH1
+
+
CH1
-
-
L+
L-
Potential equalization connection: wire cross-section ≤ 4 mm²
Internal grounding ports: wire cross-section ≤ 1.5 mm²
Controller
l
+
I = 4...20 mA
-
l
+
I = 4...20 mA
-
+
-
supply voltage
EE100Ex Safety Guide