Herunterladen Inhalt Inhalt Diese Seite drucken

Outdoor Unit Configuration; Selection Of Installation Site - Mitsubishi Electric CITY MULTI PUHY-YSMF-B Installationshandbuch

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

4. Outdoor unit configuration

The unit (PUHY-600/650/700/750YSMF-B) consists of a combination of variable capacity units (PUHY-400/500YMF-B) and constant capacity units
(PUHN-200/250YMF-B). A CMC-30A (optional) is required when using a combination of these units.
Super Y
Variable capacity unit
PUHY-600YSMF-B
PUHY-400YMF-B
PUHY-650YSMF-B
PUHY-700YSMF-B
PUHY-500YMF-B
PUHY-750YSMF-B
CMC-30A (optional)
Name
Shape
CMC-30A
Name
Shape
CMC-30A

5. Selection of installation site

Select space for installing outdoor unit, which will meet the following
conditions:
no direct thermal radiation from other heat sources
no possibility of annoying neighbors by noise from unit
no exposition to strong wind
with strength which bears weight of unit
note that drain flows out of unit when heating
with space for air passage and service work shown below
Because of the possibility of fire, do not install unit to the space where
generation, inflow, stagnation, and leak of combustible gas is ex-
pected.
Avoid unit installation in a place where acidic solution and spray (sulfur)
are often used.
When having cooling operation at an outside air temperature of be-
low 10°C, in order to obtain steady operation of unit, select an instal-
lation site not exposed directly to rain and snow, or install air outlet
and inlet ducts. (Refer to Page 11 .) Install the outdoor unit at the
same position on the same floor, or above, the indoor unit. (See the
figure at the right.)
Do not use unit in any special environment where oil, steam and
sulfuric gas exist.
6
Constant capacity unit
PUHN-200YMF-B
PUHN-250YMF-B
PUHN-200YMF-B
PUHN-250YMF-B
1 Distributer (gas)
2 Oil balance pipe 2
1
5 Connecting pipe
6 Connecting pipe
1
3 Distributer (liquid)
1
1
7 Connecting pipe
1
1
Installation restriction on outdoor unit when cooling operation is performed
when the outdoor air temperature is 10°C or lower.
A
(Same floor as indoor unit, or floor above)
A 4 m or less
4 Connecting pipe
1
8 Elbow
2

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

City multi puhy-p-ysmf-b

Inhaltsverzeichnis